Skip to main content

May 2016 Hole Notes

Page 34

Duct tape not cutting it another season? Can’t squeeze one more pass out of that worn out mower? It’s time!! Newer equipment is NOT out of your budget! Make ONLY 3 PAYMENTS this year (June, August, October). Then 2 or 3 additional seasons, customized to your needs. That’s it. We have the equipment and the financing solutions to help. Call us today! Adam Hoffman Ph: 612-802-3149 • Nick Sherer Ph: 612-308-0102 • Mitch Stewart Ph: 515-240-8874 PAR AIDE

1 7 1 0 A l e x a n d e r R o a d • E a g a n , M N 5 5 1 2 1 • w w w. Tu r f w e r k s . c o m

ed’, as indicated by a wavy red line at point “AA”, the electron path of least resistance is through the shorted path, thus avoiding the solenoid’s 30 ohms resistance. Such a shorted path would cause a resistance measurement of one ohm or less, typically blow a fuse in the controller, or be registered as a short by the controller’s internal diagnostics if so equipped. A short occurring at Point “BB” would, when Circuit 1 is activated, would also activate Circuit 2. Likewise, as when Circuit 2 is activated, Circuit 1 would also activate. Depending upon the electrical capacity

Page 34

of the controller, you may immediately blow a fuse, operate with both circuits operating when either one is activated, or cause the controller’s transformer to run warm/hotter than normal – which may damage the transformer over the long run. Multimeter Measurements: When using a multimeter to measure the circuit’s ohm resistance measurements, the expected multimeter measurement for Circuit 1 is 30 ohms and for Circuit 2 is 10 ohms. However, if there is a short at loca-


Turn static files into dynamic content formats.

Create a flipbook